Release Notes > KEPServerEX 6.7.1046.0
KEPServerEX 6.7.1046.0
Version 6.7.1046.0
June 27, 2019
General
OS Support
Microsoft Windows Server 2019 and Windows 10 IoT Enterprise are now included in the list of supported operating systems.
Configuration
Security / UI Improvements
The Secure Installation Guide has been updated to reflect best practices for controlling access to KEPServerEX for administrative and non-administrative users.
Event Log default column width has been changed to better support HiDPI displays.
Fixed several abbreviation and truncation issues for ongoing multilingual support.
Detail View enhancement: “Jump To”
A user can now start typing the item name they wish to navigate to within the detail view, and the server will select that item’s location.
This functionality models Windows Explorer when attempting to find a file in long list of files.
If no item begins with the characters being typed the system will play a default notification sound.
Changes have been made to alert users to potential security concerns. Several warning dialogs have been added when configuration changes are made that would result in a decreased security posture.
All Drivers
Fixes
Fixed a memory management routine that could cause heap corruptions.
Resolved a heap corruption that could crash the runtime for certain drivers. The issue was discovered in a project using the Modbus Ethernet driver.
Fixed an issue that could affect serial drivers when using Ethernet Encapsulation where drivers could fail the first transmit (TX) if the device reset (RST) the connection. Ethernet Encapsulation will now attempt to reconnect before failing the TX.
ABB Totalflow
Updates
Resolved an issue introduced in the 6.5.829.0 release where the driver could stop processing new read requests on existing devices and show the channel level _PendingReads tag as stuck. This usually happened following EFM read attempts that were interleaved with real time reads.
Corrected an issue introduced in the 6.6.348.0 release where the driver could endlessly retry if receiving responses (noise) but with no valid data from the device.
Enhanced the driver to support an older version of firmware for liquid meters, which corresponds to ABB extradata.ini revision #52.
Allen-Bradley ControlLogix Ethernet
Guardlogix L43S
Fixed an issue with reading arrays from Guardlogix L43S Controllers.
Allen-Bradley DF1
Connect Attempts
Expanded the Connect Attempts feature introduced for Ethernet Encapsulation in the 6.6.348.0 release to honor the connection timeout when not connected.
DataLogger
Updates
Configuration settings can now be set through the Configuration API service.
Feature translation for all languages currently supported by the server.
Removed CSV Import and Export feature. Added help information on importing via JSON and the Configuration API.
Added full configuration of DataLogger through JSON files.
Updated the user interface to conform to Version 6 styling.
Enhanced the plug-in to be able to log Complex tags from the Advanced Tags plugin.
EFM Exporter
Updates
Fixed an issue where enabling/disabling and copying/pasting poll groups in the EFM exporter would sometimes cause polls to fail to initiate.
Resolved a timing issue that could prevent completion of a Poll.
Resolved a threading issue that could prevent completion of a Poll.
EUROMAP 63
Updates
Added support for enforcing a unique session range per device. This prevents overlaps when the same session directory path is defined for more than one device.
Added a property to configure the use of Report Command Cyclic Option.
Resolved an issue with commas or blank lines within a description field in a file used for automatic tag generation. These are now processed completely and correctly.
Fanuc Focas Ethernet
Updates
Added support for the following Fanuc Focas Data Window Library calls:
cnc_alarm2
cnc_diagnoss
cnc_rdaxisdata
cnc_setpath cnc_getpath
Fixed an issue where the Event Log error messages were not reporting the correct error code value.
Fisher ROC Ethernet
Updates
Added _System tags for _DeviceId and _DevicePort.
Resolved an issue where EFM uploads failed if more than 50 History Points existed in the device.
Fisher ROC Plus Ethernet
Updates
Corrected EFM exporter output for Meter Type and Calculation Method using polled device settings.
Added _System tags for _DeviceAddress and _DevicePort.
Fisher ROC Plus Serial
Meter Type
Corrected EFM exporter output for Meter Type and Calculation Method using polled device settings.
Fisher ROC Serial
50 History Points
Resolved an issue where EFM uploads failed if more than 50 History Points existed in the device.
IEC 60870-5-101 Client
ASDU Tags
Added the Control Sub-Types for Select and Deselect for all ASDU tags.
IEC 60870-5-104 Client
Updates
Added the Control Sub-Types for Select and Deselect for all ASDU tags.
Fixed an issue where a STARTDT command was not sent when reconnecting after the slave closed the connection.
IEC 61850 MMS Client
Updates
Resolved an issue where communication failures with certain devices might not set the _Error tag or post a “device not responding” message to the Event Log.
Added a new polling level setting "Attribute" that will cause objects in the hierarchy to be polled individually. Without this setting, polls of the current level in the hierarchy can fail if any poll at a lower level fails.
IoT Gateway
MQTT Agent
Enhanced the MQTT Agent to allow the use of ‘$’ in the first character of the Topic.
Lufkin Modbus
Connect Attempts
Expanded the Connect Attempts feature introduced for Ethernet Encapsulation in the 6.6.348.0 release to honor the connection timeout when not connected.
Mitsubishi CNC Ethernet
Tag Address
Expanded valid tag address range to match protocol documentation.
Modbus Serial
Connect Attempts
Expanded the Connect Attempts feature introduced for Ethernet Encapsulation in the 6.6.348.0 release to honor the connection timeout when not connected.
MTConnect
_System._Error
Fixed an issue that prevented the _System._Error tag from functioning properly.
ODBC Client
Stored Procedure
Increased the maximum length of a stored procedure parameter from 255 to 1023 characters.
OPC UA Client
Updates
Fixed a memory leak that could occur when a subscription request to monitor an item was rejected by the OPC UA Server. This issue was most apparent with a frequent high volume of "Attempt to add item failed” messages posted in the Event Log.
Added new OPC UA Security Policy (Basic256Sha256) for client configuration.
Updated the default Security Policy to use most secure (Basic256Sha256) and to use the message mode “Sign and Encrypt”.
Updated icons in server browse property to display secure Policies (Green lock icon), deprecated Policies (Yellow lock icon), and insecure Policies (red open-lock icon).
OPC UA Configuration Manager
Updates
Added a new OPC UA Security Policy (Basic256Sha256) available for server endpoint configurations.
Updated the default Security Policy to use most secure (Basic256Sha256) and to use the message mode of “Sign and Encrypt”.
Updated the UI to show Security Policies that are deprecated (Basic128Rsa15, Basic256, None).
Updated instance certificate signature algorithm to use sha256RSA for new self-signed certificates.
Changed the instance certificate expiration from ten (10) years to three (3) years.
Added a pop-up message to warn users when trusting certificates using an unsecure signature algorithm.
Scheduler
Configuration Change
Resolved an issue where the Scheduler could stop working after a configuration change to a Schedule. This problem was more common when the project was complex and contained a large number of Schedules.
Siemens TCP/IP Ethernet
Updates
Fixed an issue introduced in 6.4. Now S7 String type tag addresses that do not contain a “.LEN” specifier will function correctly when the PDU size of 240 is negotiated by the device or manually set by the user from the Maximum PDU Size parameter in device properties.
Added support for Multiple Non-Redundant 400 CPUs.
TIA Portal Exporter Utility
Tag Comments are now exported in the project's Reference Language by default.
Added support for Siemens TIA Portal v15.0.0.1 through v15.0.0.4.
Added support for Siemens TIA Portal v15.1.0.0.
Torque Tool Ethernet
Updates
Added support for the following MIDs:
MID8 for Generic Subscribe messages
MID1201 and 1202 for Overall Operation Result Messages
MID224 and 225 for Set and Reset of Digital Input Functions
MID250 and MID251 for Socket Selector Information messages
MID254 and 255 for Socket Selector Red and Green Lights
Added support for new message revisions in the following command sets:
MID2 revisions 3 through 6
MID41 revisions 2 through 5
MID65 revision 7
MID71 & MID76 revision 2 and 3
Fixed the following defects:
Writing a bad value to a tag would cause other tags to have bad quality.
MID211 responses were being malformed when populating tag data.
MID40 Tool Data requests now respect client update rates.
Toyopuc PC3/PC2 Ethernet
Updates
Increased maximum Channel count to 256.
Fixed an issue that could cause the driver to stop requesting tags.
Weatherford 8500
Connect Attempts
Expanded the Connect Attempts feature introduced for Ethernet Encapsulation in the 6.6.348.0 release to honor the connection timeout when not connected.
Was this helpful?