Kepware Drivers > S Drivers > SattBus Ethernet > Setup > Device Properties — Communication Properties > Changing the Local Port Number and Network Adapter Properties
Changing the Local Port Number and Network Adapter Properties
For information on changing the Local Port Number and the Network Adapter properties, refer to the instructions below.
 
Changing the Local Port Number Property
1. To start, right-click on the device and then select Properties.
2. Next, click on the Communication Parameters property group and refer to the Port Number field.
3. Make changes to the property as desired by typing the number or using the arrows to the right. Caution: Some SattBus Ethernet modules are configured to send responses to a fixed, predefined port number (such as 2999) on the PC. As such, when the local port number is changed, the bind may succeed although the actual communications fail.
Changing the Network Adapter Property
1. To start, right-click on the channel and then select Properties.
2. Next, click on the Ethernet Settings property group and refer to the Network Adapter field. Note: If only a single Network Interface Card (NIC) is in the machine, users will have to multi-home the PC. Once completed, the "Default" adapter should not be selected for any of the other channels.
 
Was this helpful?