ROC Point Types
ROC Point Types
The availability of point types varies by model and by how the particular unit is equipped. Points may be physical I/O or internal I/O.
 
Physical I/O Points
Physical I/O points are one of Discrete Inputs (type 1), Discrete Outputs (type 2), Analog Inputs (type 3), Analog Outputs (type 4) and Pulse Inputs (type 5). The logical address for physical I/O points is based on their position in the unit, known as point number. There are four slots for each rack. The I/O field is not typically fully populated.
Note: Rack and slot are ROC nomenclature; however, many ROC devices have no physical racks or slots.
 
Logical addresses are calculated from the point number reference. For information on reconciling the point number to the logical address, refer to the table below.
 
ROCLINK Point Number
Server Logical Address
A1-A16
0-15
B1-B16
16-31
C1-C16
32-47
D1-D16
48-63
E1-E16
64-79
...
...
 
For example, an I/O point with ROCLINK 800 point number "A5" would be logical address "4". An I/O point with ROCLINK 800 point number "C5" would be logical address "36" by the function A + B + C5 (or 15+16+5=36).
 
Internal I/O Points
Internal I/O points consist of PID settings, system flags, communications parameters and other internal information. The internal I/O logical address begins at 0 for each point type. A ROC unit may have one or several of a given internal point type. Each point type has a specific set of parameters. ROC drivers have no array types.
 
Point Type Tables
 
ROC Point Types for ROC300-Series
For a detailed listing of all point type parameters' access, data type, length, and description; refer to the device's ROC Protocol User Manual.
 
Point Types
Description
ROC300-Series FlashPAC
ROC300-Series ROCPAC
0
Configurable Opcode
Yes
Yes
1
Discrete Inputs (DI)
Yes
Yes
2
Discrete Outputs (DO)
Yes
Yes
3
Analog Inputs (AI)
Yes
Yes
4
Analog Outputs (AO)
Yes
Yes
5
Pulse Inputs (PI)
Yes
Yes
6
Proportional, Integral and Derivative (PID) Control
Yes
Yes
7
American Gas Association (AGA) Flow Parameters
Yes
Yes
9
Local Display Panel
Yes
Yes
10
AGA Flow Values
Yes
Yes
11
Tank Parameters
No
Yes
12
ROC Clock
Yes
Yes
13
System Flags
Yes
Yes
14
Communication Ports
Yes
Yes
15
System Variables (ROC Information)
Yes
Yes
16
Function Sequence Table (FST) Parameters
Yes
Yes
17
Soft Points
Yes
Yes
18
AI Calibration
No
Yes
19
Database Setup
Yes
Yes
20
ROC Tasks
Yes
Yes
21
Information for User-Defined Points
Yes
Yes
22-31
User-Defined Points
No
No
32
User Defined Typically Modem Config for COM1
Yes
Yes
33
User Defined Typically Modem Config for LOI and COM2
Yes
Yes
34
User Defined Typically Modbus Config for COM1
Yes
Yes
35
User Defined Typically Function Config for COM1
Yes
Yes
36
User Defined Typically Host Config for COM1
Yes
Yes
37
User Defined Typically Modbus Config for LOI and COM2
Yes
Yes
38
User Defined Typically Function Config for LOI and COM2
Yes
Yes
39
User Defined Typically Host Config for COM1
Yes
Yes
40
Multi-Variable Sensor (MVS) Parameters
Yes*
No
41
AGA Run Parameters
Yes
No
42
Extra Run Parameters
Yes
No
44
Power Control
Yes
No
49
Upload to Disk
No
No
50
Download to ROC
No
No
56
AI Calibration
Yes
No
57
Keypad / Login Security Parameters
Yes
No
59
Program Flash Control Parameters
Yes
No
 
*Added via a user program.
 
ROC Point Types for FloBoss 100-Series, FloBoss 407, and FloBoss 500-Series
Point Types
Description
FloBoss 100-Series
FloBoss 407-Series
FloBoss 500-Series
0
Configurable Opcode
Yes
Yes
Yes
1
Discrete Inputs
Yes
Yes
Yes
2
Discrete Outputs
Yes
Yes
Yes
3
Analog Inputs
Yes
Yes
Yes
4
Analog Outputs
Yes
Yes
Yes
5
Pulse Inputs
Yes
Yes
Yes
6
PID Control*
Yes
Yes
Yes
7
AGA Flow Parameters*
Yes
Yes
Yes
8
History Parameters
Yes
No
Yes
10
AGA Flow Values*
Yes
Yes
Yes
12
ROC Clock
Yes
Yes
Yes
13
System Flags
Yes
Yes
Yes
14
Communication Ports
Yes
Yes
Yes
15
System Variables (ROC Information)
Yes
Yes
Yes
16
FST Parameters
Yes
Yes
Yes
17
Soft Points
Yes
Yes
Yes
19
Database Setup
Yes
Yes
Yes
20
ROC Tasks
Diagnostics
No
Yes
Yes
No
No
No
21
Information for User Defined Points
Yes
Yes
No
22-23
User Defined Points
No
No
No
24
Reserved
N/A
N/A
N/A
25–31
User Defined Points
No
No
No
32
User Defined – Typically Modem Config for COM1
Yes
Yes
No
33
User Defined – Typically Modem Config for LOI and COM2
Yes
Yes
No
34
User Defined – Typically Modbus Config for COM1
Yes
Yes
No
35
User Defined – Typically Function Config for COM1
Yes
Yes
No
36
User Defined – Typically Host Config for COM1
Yes
Yes
No
37
User Defined – Typically Modbus Config for LOI and COM2
Yes
Yes
No
38
User Defined: Typically Function Config for LOI and COM2
Yes
Yes
No
39
User Defined – Typically Host Config for COM1
Yes
Yes
No
40
Multi-Variable Sensor (MVS) Parameters
Yes
Yes
No
41
AGA Run Parameters*
Yes
Yes
Yes
42
Extra Run Parameters*
Yes
Yes
Yes
43
User Lists
Yes
Yes
Yes
44
Power Control
Yes
Yes
Yes
45
Meter Calibration and Sampler
Yes
No
Yes
46
Meter Configuration Parameters
Yes
No
Yes
47
Meter Flow Values
Yes
No
Yes
48
PID Control Parameters
Yes
No
Yes
49
Upload to Disk
No
No
No
50
Download to ROC
No
No
No
52
Battery Parameters
No
No
Yes
53
Modbus Configuration Parameters
Yes
No
Yes
54
Modbus Function Tables
Yes
No
Yes
55
Modbus Special Function Table
Yes
No
Yes
56
AI Calibration
Yes
Yes
Yes
57
Keypad / Login Security Parameters
Yes
Yes
Yes
58
Revision Information
Yes
No
Yes
59
Program Flash Control Parameters
Yes
Yes
Yes
60-77
SAM User Defined Parameters
No
No
No
80
Enhanced Communication (ECM) Parameters
Yes
No
No
85
HART Parameters
Yes
No
No
86
Extended History Parameters
Yes
No
No
88
BLM User Lists
Yes
No
No
89
Chart User List Parameters
Yes
No
No
93
License Key Information Parameters
Yes
No
No
94
User C Program Parameters
Yes
No
No
98
Extended Soft Point Parameters
Yes**
No
No
117
Modbus Configuration Parameters
Yes
No
No
118
Modbus Register Mapping Parameters
Yes
No
No
120
Modbus Client Modem Configuration
Yes
No
No
121
Modbus Client Polling Table Configuration Parameters
Yes
No
No
122
DS800 Configuration Parameters
Yes
No
No
 
*FloBoss 100-Series and FloBoss 500-Series Backward Compatibility.
**This point type is only supported by FloBoss 107.
 
ROC Point Types for RegFlo
Point Types
Description
Point Types
Description
0
Configurable Opcode
17
Soft Points
1
Discrete Inputs
19
Database Setup
2
Discrete Outputs
56
AI Calibration
3
Analog Inputs
57
Keypad / Login Parameters
4
Analog Outputs
80
Regulator Parameters
8
History Parameters
81
Logic Alarm Parameters
 